High Static Pressure Duct R32 Deluxe Model - S-125PE3R (U-125PZH3R5)
Energy Efficient
Enhanced
Surespec | : |
0721-Packaged air conditioning
|
Speedspec | : |
15738-Domestic airconditiong
|
Warranty | : | 5 years |
Colour | : | Black |
Features | : | Ducted |
Number of Fan Speeds | : | 3 |
Weight | : | 41 kg |
Length | : | 700 mm |
Width | : | 1200 mm |
Maximum Chargeless Length | : | 30 m |
Pipe Length Range | : | 5 m - 85 m |
Elevation Difference (OU located lower, OU located higher) | : | 15 m | 30 m |
Drain Piping | : | VP-25 |
Piping Connections | : | Liquid: Ø 9.52 mm | Gas: Ø 15.88 mm |
Outdoor DImensions | : | 1,416 mm x 940 mm x 340 mm |
Refrigerant at Shipping / Additional Gas Amount | : | R32 3,050 / 45 (g/m)g |
Indoor Dimensions | : | 360 mm x 1200 mm x 700 mm |
Outdoor Weight | : | 99 kg |
Heating output | : | 14.0 kilowatts |
Cooling output | : | 12.5 kilowatts |
Operating Range Cooling : Heating | : | -15˚C to 48˚C : -20˚C to 24˚C |
Outdoor Sound Power Level (H/M/L) Cooling : Heating | : | 69 (67) : 69 (67) dB |
Indoor Sound Power Level (H/M/L) Cooling : Heating | : | 71 / 69 / 67 : 71 / 69 / 67 dB |
Outdoor Sound Pressure Level (Silent mode) Cooling : Heating | : | 53 (51) : 53 (51) dB(A) |
External Static pressure | : | 100 (10 - 150) pa |
Indoor Sound Pressure Level (H/M/L) Cooling : Heating | : | 49 / 47 / 45 : 49 / 47 / 45 dB(A) |
Current (rated) Cooling : Heating | : | Indoor: –*4 | Outdoor: 16.7 : 17.6 | 16.0 : 16.8 |
Air Volume (H/M/L) Cooling : Heating | : | Indoor: 835 / 768 / 601 : 835 / 768 / 601 | Outdoor: 2,087 : 1,870 |
Power Source | : | 1 Phase / 50Hz 230V | 240V |
EER : COP | : | 3.57 : 3.80 W/W |
COP@H2 condition | : | 2.72 W/W |
Total Power Input | : | 3.50 : 3.68 kW |
Capacity | : | 12.5kW |
TCSPF : HSPF Commercial | : | Hot Climate: 5.36 : 5.23 / Average Climate: 5.55 : 4.80 / Cold Climate: 5.97 : 4.31 |
TCSPF : HSPF Residential | : | Hot Climate: 4.92 : 5.17 / Average Climate: 4.49 : 4.40 / Cold Climate: 4.60 : 3.90 |